• Pure static bypass switch without bridging contactor securing a fast and reliable transfer to and from bypass, rated for 125% nominal load.
• Automatically starts up the connected equipment upon the return of utility power.
• ECO Mode: Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection.
• Input power factor correction: Minimizes installation costs by enabling the use of smaller generators and cabling.
• Intelligent battery management: Maximizes battery performance, life, and reliability through intelligent, precision charging.
• Intelligent Card Slot: Customize UPS capabilities with management cards.
• LCD graphics display: Text and mimic diagrams that display modes of operation, system parameters and alarms.
• Serial connectivity: Provides management of the UPS via a serial port.
Specifications
• Max Configurable Power (Watts): 1.6kWatts / 2.0kVA
• Output Voltage Note: Configurable for 220 : 230 or 240 nominal output voltage
• Efficiency at Full Load: 88.0 %
• Input frequency: 40 - 70 Hz Auto sensing
• Input voltage range for main operations: 110 - 285 Half load, 160 - 280 Full loadV
• Typical recharge time: 5.5hour(s)
• Nominal Battery Voltage: 72 V
• Surge energy rating: 600J
• Output Connections: 4 x IEC 60320 C13