Schneider Electric EasyPact Molded-Case Circuit Breaker, TMD, 1P 1d


[In] Rated Current: 15A
Price:
Sale price

Description

• Work below rated operational voltage(Ue) 415VAC at 50/60Hz or 125VDC network.
• Is designed one pole frame with detection on one pole, equipped TMD trip unit for thermal-magnetic protection.
• This device is certified for operation in pollution degree III environment as defined by IEC60947, and pass the test of extremely atmospheric conditions.
• Can be mounted vertically or horizontally in a metal enclosure, and against from safety risk by padlocking.
• The degree of protection is IP40 for direct rotary handle, and IP54 for extended rotary handle.

Specifications
• Device application: Distribution
• Poles description: 1P
• Protected poles description: 1t
• Network type: DC / AC
• Network frequency: 50/60 Hz
• [In] rated current: 15 A at 40 °C
• [Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
• [Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2
• [Ue] rated operational voltage: 125 V DC conforming to IEC 60947-2 / 415 V AC 50/60 Hz conforming to IEC 60947-2
• Standards: EN/IEC 60947-2 / JIS C8201-2-2 / GB/T 14048.2 / EN/IEC 60947-1
• Breaking capacity: 25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 / 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 / 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 / 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 / 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)